Milesight

CT305 Milesight 500A Smart Current Transformer

500A Smart Current Transformer

Order codeCT305 In stockOfficial distributor

The CT305 is a 500A Smart Current Transformer. With a 500 A range and a Φ36.5 mm wire hole, it is sized for area-level monitoring and medium-to-large equipment groups with higher power demand.

  • LoRaWANLoRaWAN®
  • PowerInduced current from
  • ProtectionIP30
  • Operating–20 … +1 °C
  • In stockVilnius warehouse · EU
  • In stockLondon warehouse · UK

Dispatch and lead time are confirmed in the quote.

EasyNet Technologies
  • Official distributor
  • 17+ years in IoT
  • Installation support

Manufacturer warranty24 months

Milesight

Overview

CT305 overview

Overview

The CT305 is a LoRaWAN three-phase smart current transformer for wireless energy monitoring and usage analysis. With a 500 A range and a Φ36.5 mm wire hole, it is sized for area-level monitoring and medium-to-large equipment groups with higher power demand.

Three-Phase, Self-Powered Monitoring

A one-to-three clamp design measures up to three phases at once, and the device harvests power directly from the measured circuit, eliminating batteries and external wiring while keeping continuous operation.

High-Accuracy Measurement

With ±1% accuracy, sampling up to 3.3 kHz and a 1 s sampling rate, the CT305 reports RMS current and accumulated ampere-hours in real time for detailed energy analysis.

Smart Alerts

Configurable threshold, over-current, wire-temperature and low-voltage alerts (with an LED indicator) enable swift action, with an optional external NTC sensor for cable temperature.

Non-Invasive Installation

The split-core clamp attaches around existing wires without de-energizing the circuit, so it deploys quickly in distribution boxes for retrofit projects without downtime.

Integration

Compliant with standard LoRaWAN gateways and the Milesight Development Platform, the CT305 forwards data to BMS or energy-management systems for centralised monitoring.

Key features

Three-phase measurement

Three-phase measurement (one-to-three clamps).

Self-powered from the measured circuit

Self-powered from the measured circuit, no batteries.

± 1% accuracy

± 1% accuracy, up to 3.3 kHz sampling.

Real-time accumulated ampere-hours

Real-time accumulated ampere-hours (1 s).

Threshold

Threshold, over-current, temperature & low-voltage alerts.

Non-invasive split-core clamp install

Non-invasive split-core clamp install.

Optional external wire temperature sensor

Optional external wire temperature sensor.

FUOTA firmware updates

FUOTA firmware updates.

Technical data

CT305 specifications

Specifications
Detection ParameterRMS current
Sampling Frequency3.3 kHz
Working Frequency50 ~ 60 Hz
Rated Primary Current (per CT)500 Arms
Rated Secondary Current150 mArms
Minimum Reporting Current5 Arms (1 min interval); 4.5 Arms (10 min interval)
Accuracy± 1%
Resolution1 mA
Temperature Sensor1 × NTC sensor, −20 °C ~ 100 °C, ± 1% (optional)
Specifications
ProtocolLoRaWAN®
Antenna Connector1 × 50 Ω SMA connector (centre pin: SMA female)
FrequencyCN470/IN865/RU864/EU868/US915/AU915/KR920/AS923-1&2&3&4
Tx Power16 dBm (868 MHz) / 20 dBm (915 MHz) / 19 dBm (470 MHz)
Sensitivity−137 dBm
ModeOTAA/ABP Class A

Applications

CT305 applications

Smart Buildings

Floor-level distribution panels and grouped HVAC equipment are monitored phase by phase to track energy trends and detect anomalies, all without power interruption.

Facilities & Plant

Chiller pumps, cooling tower systems and production lines gain non-invasive current monitoring for status detection and predictive maintenance.

Energy Management

Real-time ampere-hour tracking supports energy-saving programmes and load analysis across areas, with wireless LoRaWAN backhaul.

Retrofit Projects

Split-core clamps fit existing wiring in commercial and industrial sites, enabling fast deployment without cutting wires or shutting down equipment.

Questions

CT305 questions and answers

How is the CT305 powered?

Induced current from, according to the specification.

What ingress protection does the CT305 have?

IP30, according to the specification.

What is the operating temperature of the CT305?

–20 … +1 °C, according to the specification.

What lorawan does the CT305 provide?

LoRaWAN®, according to the specification.

Request a quote

CT305 price and lead time

Tell us the quantity and the delivery country. We reply within one working day with the price, stock at the nearest warehouse and the dispatch date.

  • Company code306755852
  • VAT numberLT100017217417
EasyNet Technologies
  • Official distributor
  • 17+ years in IoT
  • Installation support

Manufacturer warranty24 months

Milesight

Quote request

Requesting CT305

We reply within one working day. We use these details only to answer this enquiry. See the Privacy Policy.

Europe & United Kingdom

A local team.
A direct conversation.

Product advice, availability and project enquiries.

All contact details