Remote device data acquisition
Remote device data acquisition.

IoT Controller
The UC300 is an IoT Controller. It includes digital inputs and relay outputs for controlling devices, along with RS232 and RS485 serial ports for communication with industrial machines.
Dispatch and lead time are confirmed in the quote.
Manufacturer warranty24 months
Overview
The UC300 Series is an industrial IoT controller designed to connect field devices and transfer their data to remote systems. It collects information from sensors, machines, and other equipment and sends it to monitoring platforms for analysis and control. This allows operators to observe equipment status and trigger actions without being physically present.
The device also supports local automation. Trigger conditions and actions can be configured so the controller continues operating even if the network connection is temporarily unavailable. This enables reliable control in environments where connectivity may occasionally drop.
The controller can transmit device data through either LoRaWAN® networks or cellular connectivity such as 4G LTE with fallback to 3G or 2G. This flexibility allows deployment in different environments, from private LoRaWAN networks inside facilities to wide-area cellular coverage.
For cellular versions, a Micro-SIM card is used to access mobile networks. The device can send data through standard communication methods including TCP, UDP, MQTT, SMS, or cloud platforms such as Milesight IoT Cloud. These options make it easy to integrate the controller with monitoring systems and industrial platforms.
The UC300 Series supports multiple trigger conditions and automated actions. This means events such as sensor readings, digital input changes, or scheduled timers can automatically initiate responses like activating outputs or sending data reports.
A built-in watchdog mechanism helps maintain stable operation by monitoring the system and automatically recovering from unexpected errors. This improves reliability in industrial environments where continuous operation is important.
The controller supports a wide range of industrial interfaces for connecting external equipment. It includes digital inputs and relay outputs for controlling devices, along with RS232 and RS485 serial ports for communication with industrial machines.
Analog inputs support both 4–20 mA and 0–10 V signals, which are commonly used by industrial sensors. The device also includes PT100 RTD temperature inputs capable of measuring temperatures from –200 °C to 800 °C. These options allow the controller to collect data from many types of sensors and equipment in a single system.
The UC300 Series is designed for indoor industrial environments. It operates on a wide 5–24 V DC power input and supports operating temperatures from –20 °C to +60 °C.
The device uses a metal enclosure with an IP30 protection rating and supports multiple installation options including desktop placement, wall mounting, or DIN rail mounting. Its compact size of 93 × 70 × 22 mm allows it to fit easily inside control cabinets or equipment panels.
Remote device data acquisition.
Autonomous trigger-based control actions.
Remote monitoring via IoT cloud.
Multi-interface device integration.
Network-independent local operation.
5–24 V DC power supply.
–20 °C to +60 °C operating range.
IP30 metal enclosure.
Technical data
| Wireless Transmission | |
|---|---|
| Technology | LoRaWAN®, LoRa D2D |
| Antenna Connector | 1 × 50 Ω SMA Connector (Centre PIN: SMA Female) |
| Frequency | CN470/IN865/EU868/RU864/US915/AU915/KR920/AS923-1&2&3&4 |
| Tx Power | 16dBm (868MHz)/22dBm (915MHz)/19dBm (470MHz) |
| Sensitivity | -137dBm @300bps |
| Mode | OTAA/ABP Class C |
| Advanced Feature | LoRa D2D Controller, LoRa D2D Agent |
| Cellular Model | |
| Network | 4G LTE/3G/2G |
| Antenna Connector | 1 × 50 Ω SMA Connector (Centre PIN: SMA Female) |
| SIM Slot | 1 (Micro SIM-3FF) |
| Application Mode | TCP/UDP/MQTT/AWS/Milesight IoT Cloud/SMS |
| Data Interfaces | |
| Interface Type | 3.5mm Terminal Block |
| IO | |
| Ports | 4 × DI + 2 × DO |
| Digital Input | Opto-isolated Digital Inputs, 3-24VDC (pulse counter support) |
| Digital Output | SPDT Relay Contact Rating: 3A@DC Max: 30 V or AC Max: 250 V |
| Serial Port | |
| Ports | 1 × RS232 + 1 × RS485 |
| Baud Rate | 1200~115200 bps |
| Protocol | Transparent (RS232), Modbus RTU (RS485) |
| Analog Input | |
| Ports | 2 × 4~20 mA + 2 × 0~10 V |
| Resolution | 12 bit |
| Analog Input (RTD) | |
| Ports | 2 × PT100 RTD Input |
| Input Connections | 2, 3-wire |
| Resolution | 12 bit |
| Range | -200 °C ~ 800 °C |
| Others | |
| Configuration Port | 1 × Type-C |
| LED Indicators | 1 × System, 1 × ACT |
| Built-in | Watchdog, Timer |
| Physical Characteristics | |
| Power Connector | 3.5 mm Terminal Block |
| Power Supply | 5-24 VDC |
| Colour & Material | Black, Metal |
| Ingress Protection | IP30 |
| Operating Temperature | -20 °C ~ 60 °C (-4℉ to +140℉) |
| Relative Humidity | 0% ~ 95% (non-condensing) at 25 °C/77℉ |
| Dimensions | 93 × 70 × 22 mm (3.66 × 2.76 × 0.87 in) |
| Installation | Desktop, Wall Mounting, DIN Rail Mounting |
No specification rows match the filter.
Applications
In factory environments, the UC300 Series can collect data from industrial machines and sensors through analog, digital, or serial interfaces. Information such as equipment status, sensor measurements, and operational signals can be transmitted to monitoring platforms. This helps operators supervise production processes and respond quickly to changes.
The controller can integrate with building systems that monitor temperature, environmental sensors, or control signals. By connecting these devices to a central monitoring platform, facility managers can track building conditions and automate control actions remotely.
Many industrial machines provide signals through RS232, RS485, or analog outputs. The UC300 Series can capture this data and send it to a remote management system, allowing operators to monitor equipment performance and detect operational issues early.
Remote infrastructure such as pumping systems, control panels, or industrial stations often require continuous monitoring. With wireless connectivity options like LoRaWAN or cellular networks, the UC300 can transmit operational data from these locations to centralised management platforms.
Facilities often rely on multiple sensors and control devices to maintain safe and efficient operations. By connecting these devices to a single IoT controller, operators can remotely observe system status, trigger automated responses, and maintain oversight of distributed equipment.
Questions
5–24 V, according to the specification.
IP30, according to the specification.
–20 … +60 °C, according to the specification.
CN470/IN865/EU868/RU864/US915/, according to the specification.
Request a quote
Tell us the quantity and the delivery country. We reply within one working day with the price, stock at the nearest warehouse and the dispatch date.
Manufacturer warranty24 months
Europe & United Kingdom
Product advice, availability and project enquiries.
All contact details